Negotiable
The date of payment from buyers deliver within days
Beijing
Long-term effective
2017-10-20 02:22
32
eastups(Ms.)
Beijing
No. 6 Northern Industry Road, Songshan Lake, Sci & Tech, Industry Park, Dongguan, Guangdong, China (523808)
MODEL | EA89160 | EA89200 | EA89250 | EA89300 | EA89400 | EA89500 | |
Capacity | 160 KVA 144 KW |
200 KVA 180 KW |
250 KVA 225 KW |
300 KVA 270 KW |
400 KVA 360 KW |
500 KVA 450 KW |
|
INPUT | |||||||
Rated voltage | 380 V / 400 V / 415 Vac | ||||||
Voltage range | 346 V ~ 456 V ( full load) 304 V ~ 346 V (power derating 10%) |
||||||
Rated frequency | 50 / 60 Hz | ||||||
Frequency range | 50 / 60 Hz ± 5 Hz | ||||||
Power factor | ≥ 0.99 | ||||||
Total harmonic distortion (THDI) | ≤ 3% | ||||||
Input current-limiting | 1.1 times of rated current (0.1 ~ 1.1 settable ) | ||||||
Rectifier delay start | 10 s (1 ~ 300 settable) | ||||||
Bypass voltage range | ± 20% (settable) | ||||||
OUTPUT | |||||||
Rated voltage | 380 V / 400 V / 415 Vac | ||||||
Voltage regulation | ± 1% | ||||||
Frequency | Synchronized with utility in mains mode; 50 / 60 Hz ± 0.1% in battery mode | ||||||
Waveform | Sinusoidal | ||||||
Crest factor | 3:1 | ||||||
Total harmonic distortion (THDV) | ≤ 2% (resistive load); ≤ 5% (non-linear load) | ||||||
Transfer time | 0 ms | ||||||
Inverter overload capability | 105% ~ 110% for 60 minutes; 110% ~ 125% for 10 minutes; |
||||||
Slight adjustment of inverter output voltage | ± 5 V | ||||||
BATTERIES | |||||||
DC voltage | 600 Vdc (support 576 Vdc / 588 Vdc / 612 Vdc / 624 Vdc) | ||||||
Number of battery | 50 pcs ( support 48 / 49 / 51 / 52 pcs) | ||||||
Charging current | Chargingrate (settable) × battery capacity (settable) × number of battery group (settable) | ||||||
Battery state display | Battery remaining capacity and backup time | ||||||
Battery self-test | Settable periodic self-test; manually configurable test time and voltage | ||||||
SYSTEM | |||||||
Efficiency | Line mode ≥ 93%, ECO mode ≥ 98% | ||||||
Max. parallel numbers | 6 | ||||||
Protections | Short-circuit, overload, overtemperature, overvoltage, undervoltage, battery low voltage and fan failure | ||||||
IP rating | IP 20 | ||||||
Display | 5.7 inches LCD touch screen | ||||||
COMMUNICAITONS | |||||||
RS232 / RS485 / dry contacts | Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 | ||||||
SNMP (optional) | Power management from SNMP manager and web browser | ||||||
OTHERS | |||||||
Operating temperature | 0 ~ 40℃ | ||||||
Storage temperature | - 25℃ ~ 55℃ | ||||||
Humidity | 0 ~ 95% (non-condensing) | ||||||
Noise level at 1 m | < 65 dB | < 70 dB | |||||
Dimensions (W×D×H) (mm) | 800 × 860 × 1700 | 1210 × 860 × 1950 | 2380 × 860 × 1950 | ||||
Packaged dimensions (W×D×H) (mm) | 900 × 1000 × 1950 | 1300 × 1000 × 2200 | 1300 × 1000 × 2200 (×2) | ||||
Net / Gross weight (kg) | 790 / 820 | 1135 / 1260 | 1275 / 1400 | 1355 / 1480 | 2090 / 2200 | 2300 / 2500 |
Download more information about this product
Any third-party trademarks shown here are for reference purposes only. We are not authorized to sell any items bearing such trademarks.